5820XL
Addressable Fire Alarm
Control System |
|
ESPECIFICACIONES:
Up to 508 addressable points.
• Uses standard wire—no shielded or
twisted pair required.
• Built-in digital communicator.
• Central station reporting by Point or
by Zone.
• Built-in synchronization for
appliances from AMSECO®,
Gentex®, Faraday, and Wheelock®
• Supports Class B (Style 4) and
Class A (Style 6) configuration for
SLC, SBUS, and Flexput circuits.
• Distributed, intelligent power.
• Drift compensation.
• Flexput™ I/O circuits.
• Eight pre-programmed output
cadences, (including ANSI-3.41),
and 4 programmable outputs.
• Built-in annunciator with 80-
character LCD display.
• RS-485 bus provides communication
to system accessories.
• Built-in RS-232 interface for
programming via PC.
• Built-in Form C trouble relay rated at
2.5 amps at 24 VDC.
• Two built-in Form C programmable
relays rated at 2.5 amps at 24 VDC.
• Supports Sounder Bases. |
|
| |
|
 |
 |
5700
Addressable Fire Alarm
Control System |
|
ESPECIFICACIONES:
• Up to 50 addressable points
• Up to 125 zones and 125 output groups
• Uses standard wire—no shielded or twisted pair required
• Built-in digital communicator.
• Central station reporting by point or by zone
• Supports Class B (Style 4) and Class A (Style 6 or 7) configuration for SLC
• Distributed, intelligent power
• Drift compensation
• 13 pre-programmed output cadences (including ANSI-3.41) and 4 programmable outputs
• Notification circuits configurable as 1 Class A (Style Z) or 2 Class B (Style Y), or auxiliary power for resettable,constant, or door holder power
• Built-in synchronization for AMSECO, Gentex®, Faraday, System Sensor® and Wheelock® appliances
• Built-in annunciator with 80-character LCD display
• RS-485 bus provides communication to system accessories
• Upload or download programming, event history, or detector status onsite or from a remote location using a PC and 5660 Silent Knight
Software Suite (SKSS)
• Improvements in SKSS deliver five times faster upload/downloads
• Built-in RS-232 interface for programming via PC
• Built-in Form C trouble relay rated at 2.5A at 27.4 VDC
• Two built-in Form C programmable relays rated at 2.5A at 27.4 VDC
• Programmable date setting for Daylight Saving Time
|
|
| |
|
 |
 |
5000
Series Telephone
Entry Control Syste |
|
ESPECIFICACIONES:
• Only resident-side telephones
will open system doors
• Door-strike time lengths are
programmable
• Programmable user codes for
keyless entry (4 - 6 digits)
• Up/Downloadable programming
with SKSS (Silent Knight
Software Suite)
• All tenant phone numbers
remain confidential
• System options and user
information is stored in flash
memory for instant recovery
after total power loss
• Postal lock installation
provisions
• 20 digit dialing capability
• Simple programming through
built-in touchpad
• 1,000 occupant capacity out of
the box. No expansion chips
required
• Each 5083/5084 can be
configured as a master or slave
(satellite) unit. Only one master
unit per system
• Up to four slave (satellite) units
can be connected to the master
unit to cover multiple entry
points, sharing a single phone
line
• Handsfree (5083) and Handset
(5084) models
• Built-in touch-tone and/or time
window controlled auxiliary relay
• Large backlit LCD display
• Surface or flush mountable
• Vandal-resistant rust-resistant
weather-resistant stainless steel
cabinets
• Braille touchpads
• 4 different greeting messages to
choose from |
|
| |
|
 |
 |
|
ESPECIFICACIONES:
• Built-in support for up to 127 Hochiki devices, expandable to 1016; or 99
IDP detectors and 99 IDP modules, expandable to 792 IDP detectors and
792 IDP modules
• All the features of the IFP-1000 Fire Alarm Control Panel combined with
a fully integrated voice evacuation system
• Built-in Digital Message Repeater using DSP technology
• Three field programmable user messages
• Upload/download voice messages using a PC and the 7780 voice
messaging application
• Program voice messages via serial interface or built-in microphone
• Support for up to eight VIP-50s (50 watt SBUS addressable amplifiers)
for a maximum of 400 watts per system
• Single enclosure for both fire and voice system control components
• On-board supervised microphone
• System can support two supervised remote microphones
(VIP-RMs)
• Up to 64 mappable speaker circuits using a combination of VIP-50s and
VIP-CE4s
• Supports 25 Vrms or 70.7 Vrms speaker circuits
• Built-in RS-232 and USB interface for programming
• Upload or download programming, event history, or detector status onsite
or from a remote location using a PC and 5650/5651 Silent Knight
Software Suite (SKSS) |
|
| |
|
 |
 |
|
Detect smoldering fires quickly and get
help fast with IntelliKnight® photoelectric
smoke detectors..
ESPECIFICACIONES:
• Low profile, 2 inches, including base
• Simple and reliable addressing without mechanical switches
• Automatic compensation for sensor contamination
• Built-in fire test feature
• Simple detector calibration testing through the control panel or remotely through a WindowsTM based computer software.
• Vandal-resistance locking features
• Field cleanable
• UL listed, meets NFPA 72 Ch 7 requirements
• CSFM approved
• MEA approved
• FM Approved
|
|
| |
|
 |
 |
SD500-PS SD500-PSDA
Addressable Pull-Station |
|
IntelliKnight's addressable pull stations combine fast response with pin-pointlocation ID.
ESPECIFICACIONES:
• UL Listed
• CSFM listed
• ADA compliant
• Key reset (Same key as Silent
Knight enclosures)
• Surface mount back box
available
• Terminals - accept up to 14
gauge wire
• Extremely easy to operate
• Corrosion-resistant gold-plated
contacts.
• Reflective label makes it easier
to locate in low light |
|
| |
|
 |
 |
| SD500-AIM/MIM
Addressable Input Modules |
|
IntelliKnight's addressable contact monitor
modules combine fast response with pinpoint location
ESPECIFICACIONES:
Single contact monitor
• Support for Class A (Style 6 & Style
7) or Class B (Style 4) wiring
• Attractive ivory cover plate with the
SD500-AIM
• Small and lightweight size allows for
flexible mounting options with the
SD500-MIM
• DIP switch programmable for fast
installation
• Up to 2500 ft wiring distance from
either input module to contact
• Use up to 14 gauge wire
• UL listed
|
|
| |
|
 |
 |
SD500-ANM
Addressable Notification
Modules
|
|
The cost effective way to expand the IntelliKnight’s notification circuits.
ESPECIFICACIONES:
• Class A (Style Z) or Class B
(Style Y) Notification Circuit.
• Flexible programming—choose
the cadence pattern (twelve
standard & four user-defined).
• Polling LED visible through cover
plate.
• UL listed, complies with NFPA
72.
• CSFM Approved.
• MEA Approved 429-92-E, Vol. 9 • Adds up to 127 independent
output circuits on each SLC loop.
• Supervised auxiliary power
source input.
• Completely supervised.
|
|
| |
|
 |
 |
SD500-ARM
Addressable Relay
Modules
|
|
Place relay applications anywhere on the IntelliKnight loop
ESPECIFICACIONES:
• Two sets of Form C contacts.
• Contacts are rated at 2A @ 30 VDC or .6A@ 120 VAC.
• Up to 127 relays can be used on each SLC loop.
• Relay programming is completely flexible—can be mapped to zone conditions.
• Polling LED visible through cover plate.
• UL listed, complies with NFPA 72.
• CSFM approved
• MEAApproved. 429-92-E. Vol. 9
• FM approved |
|
| |
|
 |
 |
SD500-LIM
Line Isolator Module |
|
Isolate SLC loop problems without
losing the entire loop
ESPECIFICACIONES:
Isolates short circuits on an
SLC loop.
• Protects other modules on the
loop so other devices
continue to operate.
• Can be used on Style 7
(Class A), and Style 4 (Class
B) wiring configurations.
• Mounts in a standard dual
gang or 4” square electrical
box.
Listings/Approvals
• UL Listed
• CSFM listed 7170-0559:143
• MEA approval 429-92-E
volume XI |
|
| |
|
 |
 |
|
ESPECIFICACIONES:
SBUS addressable, up to 8 VIP-50s per system for a total of 400
watts.
• Each VIP-50 is supervised and has 4 onboard Audio circuits
expandable to 8 with the VIP-CE4 for a system total of 64 audio
circuits.
• VIP-50 uses an easy to install wire harnes to connect the VIP-CE4
audio circuit expander.
• Can be mounted up to 6000 feet away from VIP-Series control panel.
• The VIP-50 has it’s own power supply and backup battery.
• Selectable for 25 volt or 70.7 volt operation. |
|
| |
|
 |
|
|